    How to interpret transformer oil analysis results after filtration?

    #1675
    鈴木 拓真
    Partecipante

    After filtration, check BDV (should be >60 kV), water content (<10 ppm), and total gas content. Acid number and IFT may take longer to stabilize. If oil analysis shows compliant values, the transformer is safe to energize. Fluidex also provides interpretation guidelines and custom filtration cycles for specific oil conditions.