What sampling rules apply when collecting oil for a transformer test?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What sampling rules apply when collecting oil for a transformer test?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #2410
    Luka
    Partecipante

    What sampling rules apply when collecting oil for a transformer test?

    #2411
    David
    Partecipante

    Sampling must avoid contamination, air ingress, and moisture pickup. Use clean, dry, dedicated sample bottles and tubing. Flush the sampling valve and lines first to remove stagnant oil. Collect a representative sample at steady flow without bubbles and cap immediately. Label with transformer ID, location, date, temperature, and sample point. For DGA, minimize agitation and headspace, and seal tightly to prevent gas loss. Wear gloves and keep containers out of rain and direct sun. Consistent sampling technique is essential for reliable trending.