Why is furan analysis included in transformer oil testing?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil Why is furan analysis included in transformer oil testing?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #3652
    Gareth
    Partecipante

    Why is furan analysis included in transformer oil testing?

    #3653
    Keith
    Partecipante

    Furan analysis detects degradation of cellulose paper insulation by measuring furanic compounds dissolved in oil. These compounds indicate thermal aging and loss of mechanical strength in paper insulation. Furan trends help estimate remaining life of transformer insulation and support decisions on loading, refurbishment, or replacement, especially when combined with temperature history and DGA results.