What does the degree of polymerization indicate in transformer insulating oil diagnostics?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What does the degree of polymerization indicate in transformer insulating oil diagnostics?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #3684
    Camilo
    Partecipante

    What does the degree of polymerization indicate in transformer insulating oil diagnostics?

    #3685
    Olivier
    Partecipante

    Degree of polymerization reflects the mechanical strength of cellulose paper insulation. Lower values indicate advanced aging and reduced tensile strength, increasing failure risk under mechanical stress. Although DP is measured directly on paper samples, oil based furan analysis provides an indirect indicator. DP assessment helps estimate remaining transformer life and guide refurbishment or replacement planning.

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Devi essere connesso per rispondere a questo topic.

Vuoi diventare un rivenditore Fluidex?

Compila il modulo e diventa nostro rivenditore!

    Errore: Modulo di contatto non trovato.