Marciano Girona

Отговори

Преглеждане на 15 съобщения - от 46 до 60 (от всички 72)
  • Автор
    Публикации
  • в отговор на: Which companies are major transformer oil manufacturers in India? #3036
    Marciano Girona
    Участник

    Major manufacturers and suppliers in India are typically those who produce or distribute mineral insulating oils and ester fluids that meet IS 335 or IEC aligned specifications and appear on utility qualified vendor lists. Examples often cited in the market include Apar Industries and Savita Oil Technologies. However, the correct answer for an engineering context is vendor specific: it depends on oil type, inhibited or uninhibited formulation, required testing certificates, and your end user qualification process. Many utilities also buy through approved distributors tied to batch testing and traceability requirements.

    в отговор на: What applications use Shell transformer oil products? #2944
    Marciano Girona
    Участник

    Shell transformer oils are used in power transformers, distribution transformers, and industrial transformers where a compliant insulating fluid is required for dielectric and cooling performance. Typical applications include substations, industrial plants, renewable integration transformers, and utility distribution networks. Selection depends on standard compliance, inhibitor package, and local utility specifications. In practice, engineers choose based on performance data sheet, testing certificates, and compatibility with existing oil for topping up or retrofill, rather than on brand alone.

    Marciano Girona
    Участник

    Testing detects open windings, short circuits, insulation breakdown, oil leakage, and insufficient output voltage that causes ignition failure.

    в отговор на: What tests are performed on transformer oil samples? #2581
    Marciano Girona
    Участник

    Common tests include breakdown voltage, moisture content, acidity, interfacial tension, dissipation factor or tan delta, resistivity, inhibitor content, particle count, and color. DGA measures dissolved gases for fault diagnosis. Furan analysis indicates paper insulation aging. Some programs add corrosive sulfur tests, oxidation stability, and metal content screening. The exact test slate depends on asset criticality, oil type, and regulatory requirements. Results are trended over time to support condition assessment and maintenance decisions.

    Marciano Girona
    Участник

    Transformer-based ignition systems improve reliability because they provide consistent high-voltage output, independent of minor supply fluctuations. Their robust design allows continuous operation in high-temperature environments without significant performance degradation. Compared to electronic igniters, they are less sensitive to electrical noise and moisture. This reliability ensures dependable burner ignition, reduced misfires, and lower maintenance requirements in oil burner systems.

    Marciano Girona
    Участник

    DGA analyzers measure gases that indicate faults (H?, CH?, C?H?). Fluidex partners with DGA manufacturers and supplies sampling kits for lab or on-site analysis. Proper sampling is supported via sealed valves on their purification systems.

    в отговор на: What is a hydraulic oil purification machine and when is it used? #1841
    Marciano Girona
    Участник

    It removes water, particles, and varnish from hydraulic fluids in presses, CNC, or heavy machinery. Fluidex hydraulic oil purification machines improve performance, reduce downtime, and extend oil change intervals. Ideal for maintenance departments and mobile crews.

    Marciano Girona
    Участник

    Fluidex offers BDV test kits with automatic arc detection, adjustable voltage rise rate, and IEC/IS compliance. Suitable for mineral and ester oils. Used for quality checks before transformer energization or after oil purification.

    в отговор на: What does an oil flushing unit do in hydraulic systems? #1781
    Marciano Girona
    Участник

    Oil flushing units clean hydraulic circuits by circulating oil at high speed and pressure to dislodge varnish, particles, and sludge. Fluidex offers flushing units with filtration and monitoring – ideal for system commissioning or major overhauls.

    Marciano Girona
    Участник

    Regeneration goes beyond filtration: it uses adsorption (e.g., Fuller’s earth) to restore chemical properties – like acid number, color, oxidation stability. Fluidex and GlobeCore systems integrate regeneration with vacuum treatment, turning aged oil into reusable IEC-compliant fluid.

    Marciano Girona
    Участник

    Fluidex offers transformer oil testing kits that include BDV testers, moisture meters, and sampling bottles. These are perfect for on-site quality control after filtration or during diagnostics. Kits are portable, accurate, and suitable for field techs and substation crews.

    Marciano Girona
    Участник

    Use a glass syringe or sealed bottle, ensuring no air bubbles. Fluidex purification units feature inline DGA sampling ports with vacuum lock to ensure sample purity. Sampling should be done after 20-30 min of oil circulation post-filtration.

    Marciano Girona
    Участник

    Fluidex offers compact oil cleaner machines with 600-1,200 L/h flow rate – ideal for smaller substations or local maintenance teams. They include heating, vacuum, and filtration, and can be operated by a single technician. Perfect for transformer depots or utility field teams.

    Marciano Girona
    Участник

    After filtration, collect an oil sample in a hermetically sealed BDV test cell. Test using a calibrated BDV tester with standard electrode gap (2.5 mm). Fluidex offers test kits and processing units with built-in BDV sampling ports. Typical target is ? 60 kV for new or well-treated oil. A successful BDV test confirms the oil’s insulation strength.

    Marciano Girona
    Участник

    For 35-110 kV transformers, filtration should be done at least once every 2-3 years, depending on load cycles and environmental conditions. Fluidex systems allow both offline and online filtration, so you can maintain oil condition without interrupting power supply. Regular servicing improves BDV, removes moisture, and ensures the oil stays within operational standards. Many companies now schedule filtration as part of annual preventive maintenance.