  • в отговор на: Why is oil used in transformer construction instead of air? #2667
    Raffaellino
    Участник

    Oil is used instead of air because it provides significantly higher dielectric strength and superior heat transfer. Oil fills internal voids, reducing partial discharge risk and preventing insulation breakdown. It efficiently transfers heat from windings to cooling surfaces, allowing compact designs with higher power density. Air insulation would require much larger clearances and cooling systems, making high voltage and high MVA transformers impractical. Oil also protects cellulose insulation from oxidation, extending transformer service life.

    Raffaellino
    Участник

    Substations require secondary containment such as oil pits, bund walls, liners, and oil water separators sized to hold the full oil volume plus rainwater. Fire separation, drainage control, and environmental protection regulations apply. Containment prevents soil and water contamination and supports spill response. Design must comply with local environmental and fire safety standards.

    Raffaellino
    Участник

    Common precautions include avoiding skin and eye contact, preventing inhalation of mists, using gloves and eye protection, ensuring good ventilation during handling, keeping oil away from open flames and hot surfaces, and preventing spills. MSDS also recommends proper storage in sealed containers, grounding and bonding during transfer to reduce static risk, and using absorbents and containment for leaks. It emphasizes washing after handling, safe disposal practices, and emergency measures such as first aid and firefighting guidance.

    Raffaellino
    Участник

    Field testers provide rapid screening of oil condition to support maintenance and troubleshooting. The most common function is BDV testing to estimate dielectric strength. Many portable devices also measure moisture in ppm, temperature, and sometimes conductivity or dielectric loss indicators. These tools help verify oil handling quality after filtering or filling, assess suspected moisture ingress, and decide whether a unit can remain in service until full laboratory results arrive. Field testing does not replace lab DGA, but it speeds decisions and reduces downtime during outages.

    Raffaellino
    Участник

    Typical secondary output ranges are 8,000 to 12,000 volts AC, with many systems using around 10,000 volts nominal. Secondary current is low but sufficient to sustain a spark across the electrode gap under burner conditions. Output requirements vary by burner model, electrode design, and the ignition control strategy. Some modern electronic igniters produce different waveforms, but traditional ignition transformers still cluster in the same voltage range because that level reliably ionizes air and ignites the fuel spray.

    Raffaellino
    Участник

    Thermal cycling is managed through oil circulation, cooling stages, and tank design that accommodates expansion and contraction. During peak load, hot oil rises to radiators where heat is rejected, and cooled oil returns to the windings. Forced air and forced oil systems increase heat removal when needed. Conservator systems buffer oil volume changes and reduce pressure stress. Monitoring of top oil temperature and winding hot spot estimates guides loading decisions and cooling control, limiting accelerated aging and maintaining dielectric margins.

    Raffaellino
    Участник

    An oil transformer tester measures dielectric breakdown voltage, indicating the oil’s ability to withstand electrical stress without failure. The test gradually increases voltage across electrodes immersed in oil until breakdown occurs. Results reveal contamination by moisture, particles, or degradation products. Dielectric testing is a key indicator of oil quality and insulation reliability.