How should a DGA report of transformer oil be interpreted?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil How should a DGA report of transformer oil be interpreted?

  • Questo topic ha 1 risposta, 2 partecipanti ed è stato aggiornato l'ultima volta 5 mesi fa da Gianfranco.
Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #4481
    中村 零
    Partecipante

    How should a DGA report of transformer oil be interpreted?

    #4482
    Gianfranco
    Partecipante

    Interpret DGA by trending gas concentrations and ratios over time, not by a single snapshot. Key gases indicate different fault types: hydrogen and methane often suggest low energy electrical activity or partial discharge, acetylene can indicate arcing, ethylene can indicate high temperature overheating, and CO and CO2 relate to paper insulation degradation. The report should be evaluated against the transformer’s history, load, temperature, and recent events, then combined with electrical tests and inspections to decide urgency and corrective actions.

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Devi essere connesso per rispondere a questo topic.