What does a test of transformer oil reveal about moisture, acidity and gas content?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What does a test of transformer oil reveal about moisture, acidity and gas content?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #2398
    Łukasz
    Partecipante

    What does a test of transformer oil reveal about moisture, acidity and gas content?

    #2399
    Nicolò
    Partecipante

    Moisture results indicate how wet the insulation system is and how much dielectric strength margin is being lost. High moisture accelerates paper aging and increases partial discharge risk. Acidity reflects oxidation; rising acidity suggests oil degradation and sludge formation that can block cooling paths. Gas content, especially via DGA, reveals internal fault processes. Hydrogen and methane may indicate low energy overheating or partial discharge, while ethylene and acetylene can signal high temperature faults or arcing. Trends are more valuable than single values.

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Devi essere connesso per rispondere a questo topic.

Vuoi diventare un rivenditore Fluidex?

Compila il modulo e diventa nostro rivenditore!