What does interfacial tension in transformer oil indicate about aging?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What does interfacial tension in transformer oil indicate about aging?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #3091
    Gianfranco
    Partecipante

    What does interfacial tension in transformer oil indicate about aging?

    #3092
    Luca
    Partecipante

    Interfacial tension (IFT) indicates the level of polar contaminants formed during oil oxidation and insulation aging. As transformer oil degrades, oxidation byproducts such as acids, sludge precursors, and dissolved cellulose compounds reduce IFT. A declining IFT value is an early warning of oil deterioration, often before dielectric strength drops significantly. Low IFT suggests increased risk of sludge formation, restricted cooling ducts, and accelerated thermal aging of paper insulation. Utilities monitor IFT trends alongside acidity, moisture, and DGA to determine whether oil reclamation or replacement is required.

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Devi essere connesso per rispondere a questo topic.

Vuoi diventare un rivenditore Fluidex?

Compila il modulo e diventa nostro rivenditore!

    Errore: Modulo di contatto non trovato.