What procedures apply when sampling transformer oil for laboratory testing?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What procedures apply when sampling transformer oil for laboratory testing?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #2554
    Camilo
    Partecipante

    What procedures apply when sampling transformer oil for laboratory testing?

    #2555
    David
    Partecipante

    Procedures include confirming safe access, using the correct sampling point, cleaning the valve, flushing a sufficient volume, and collecting in approved bottles for each test type. DGA samples require gas tight bottles, while moisture and acidity may use separate containers. Chain of custody documentation is completed. Samples are stored and shipped to minimize temperature swings and exposure to light. Field notes record load condition and any recent maintenance like filtration or oil top up, since those can affect lab interpretation and trending.