What risks are associated with DBDS in transformer oil?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What risks are associated with DBDS in transformer oil?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #2991
    Charles
    Partecipante

    What risks are associated with DBDS in transformer oil?

    #2992
    Jörn
    Partecipante

    DBDS, dibenzyl disulfide, is associated with corrosive sulfur behavior in some mineral oils. Under certain conditions it can contribute to the formation of conductive copper sulfide on paper insulated conductors, which increases dielectric stress and can lead to failures. Utilities manage this risk through screening tests for corrosive sulfur, use of passivators where appropriate, careful oil selection, and monitoring of sulfur related indicators. Industry guidance often references dedicated test methods and interpretation practices for corrosive sulfur risk, because the problem is chemistry and temperature dependent rather than purely electrical.

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Devi essere connesso per rispondere a questo topic.

Vuoi diventare un rivenditore Fluidex?

Compila il modulo e diventa nostro rivenditore!

    Errore: Modulo di contatto non trovato.