What tests are performed on transformer oil samples?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil What tests are performed on transformer oil samples?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #2606
    Jérôme
    Partecipante

    What tests are performed on transformer oil samples?

    #2607
    Camilo
    Partecipante

    Transformer oil samples are tested for dielectric breakdown voltage, moisture content, acidity or neutralization number, interfacial tension, dissipation factor, resistivity, and color. Dissolved Gas Analysis is used to detect internal electrical and thermal faults. Additional tests may include furan analysis for paper insulation aging, particle count, inhibitor content, and corrosive sulfur testing. The exact test package depends on transformer criticality and oil type. Results are trended over time to support condition based maintenance and asset life assessment.