When should dissolved gas analysis for transformer oil be performed?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil When should dissolved gas analysis for transformer oil be performed?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #2522
    Kamil
    Partecipante

    When should dissolved gas analysis for transformer oil be performed?

    #2523
    Báez Gabaldón
    Partecipante

    DGA is typically performed on a routine schedule based on transformer criticality, age, and loading. High value transmission transformers often use semiannual or quarterly sampling, while less critical units may be annual. DGA should also be done after major events such as through faults, overloading, relay operations, oil leaks, oil processing, or after commissioning to establish a baseline. If abnormal gases trend upward, sampling frequency increases until the condition stabilizes or corrective action is taken.

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Devi essere connesso per rispondere a questo topic.

Vuoi diventare un rivenditore Fluidex?

Compila il modulo e diventa nostro rivenditore!

    Errore: Modulo di contatto non trovato.