Why is DBDS contamination in transformer oil a concern?

Pagina iniziale FAQ Transformer Oil Maintenance Transformer Oil Why is DBDS contamination in transformer oil a concern?

Stai visualizzando 2 post - dal 1 a 2 (di 2 totali)
  • Autore
    Post
  • #3672
    Pawel
    Partecipante

    Why is DBDS contamination in transformer oil a concern?

    #3673
    Keith
    Partecipante

    DBDS, a sulfur compound, can decompose and form corrosive sulfur species that react with copper conductors, producing conductive copper sulfide deposits. These deposits reduce dielectric margins and can cause catastrophic transformer failures. Because the process can occur silently over time, utilities strictly control DBDS levels and specify non-corrosive oils or use passivators where permitted.