How are BDV, TAN, and moisture evaluated during testing of an oil transformer?

Начална FAQ Transformer Oil Maintenance Transformer Oil How are BDV, TAN, and moisture evaluated during testing of an oil transformer?

Преглеждане на 2 съобщения - от 1 до 2 (от всички 2)
  • Автор
    Публикации
  • #2412
    中村 零
    Участник

    How are BDV, TAN, and moisture evaluated during testing of an oil transformer?

    #2413
    Matthias
    Участник

    BDV is measured by applying increasing AC voltage across electrodes in a test cup until breakdown occurs, repeating several times and averaging results. TAN, meaning acidity or total acid number, is measured by titration to quantify oxidation products and acid formation. Moisture is measured using Karl Fischer titration in labs or portable moisture meters in the field. Together these values indicate dielectric margin, oxidation condition, and water contamination. Rising TAN and moisture typically reduce BDV and increase risk of partial discharge, overheating, and insulation aging.