How to interpret transformer oil analysis results after filtration?

Начална FAQ Transformer Oil Maintenance How to interpret transformer oil analysis results after filtration?

Преглеждане на 2 съобщения - от 1 до 2 (от всички 2)
  • Автор
    Публикации
  • #1674
    中村 治
    Участник

    How to interpret transformer oil analysis results after filtration?

    #1675
    鈴木 拓真
    Участник

    After filtration, check BDV (should be >60 kV), water content (<10 ppm), and total gas content. Acid number and IFT may take longer to stabilize. If oil analysis shows compliant values, the transformer is safe to energize. Fluidex also provides interpretation guidelines and custom filtration cycles for specific oil conditions.

Преглеждане на 2 съобщения - от 1 до 2 (от всички 2)
  • Трябва да влезете в профила си, за да отговорите в темата.

Become a Fluidex dealer ?

Fill out the form and become our dealer!

      Fluidex