What technical data is included in an oil filled transformer specification?

Начална FAQ Transformer Oil Maintenance Transformer Oil What technical data is included in an oil filled transformer specification?

Преглеждане на 2 съобщения - от 1 до 2 (от всички 2)
  • Автор
    Публикации
  • #3500
    Raffaellino
    Участник

    What technical data is included in an oil filled transformer specification?

    #3501
    Gioele
    Участник

    A specification typically includes kVA rating, primary and secondary voltages, frequency, vector group, impedance, cooling class, temperature rise, insulation levels, tap range and tap changer type, losses, efficiency, sound level, and short circuit withstand. For oil systems it includes oil type, oil volume, conservator or sealed tank design, breather type, expansion and pressure relief devices, radiators and fans, and instrumentation such as oil level, top oil temperature, winding temperature, and alarms. It also defines testing requirements, documentation, and environmental containment expectations.

Преглеждане на 2 съобщения - от 1 до 2 (от всички 2)
  • Трябва да влезете в профила си, за да отговорите в темата.

Become a Fluidex dealer ?

Fill out the form and become our dealer!

      Fluidex

      Свържете се с нас!