How does DGA oil transformer analysis help detect internal transformer faults?

Home FAQ Transformer Oil Maintenance Transformer Oil How does DGA oil transformer analysis help detect internal transformer faults?

Viewing 2 posts - 1 through 2 (of 2 total)
  • Author
    Posts
  • #3365
    Hubert
    Participant

    How does DGA oil transformer analysis help detect internal transformer faults?

    #3366
    Camilo
    Participant

    Dissolved Gas Analysis (DGA) measures fault gases generated when insulation is stressed by heat or electrical discharge. Overheating tends to raise gases like ethylene and methane, while arcing produces acetylene. Rising hydrogen can indicate partial discharge or low energy faults. By tracking concentrations and trends, DGA can warn of developing problems before they cause catastrophic failure. Interpreting DGA alongside load history, temperature, and other oil tests helps pinpoint likely fault type and urgency of maintenance action.

Viewing 2 posts - 1 through 2 (of 2 total)
  • You must be logged in to reply to this topic.

Become a Fluidex dealer ?

Fill out the form and become our dealer!

      Fluidex

      Contact us!