What does a breakdown voltage test of transformer oil measure?

Home FAQ Transformer Oil Maintenance Transformer Oil What does a breakdown voltage test of transformer oil measure?

Viewing 2 posts - 1 through 2 (of 2 total)
  • Author
    Posts
  • #3562
    Jérôme
    Participant

    What does a breakdown voltage test of transformer oil measure?

    #3563
    Galasso Guidone
    Participant

    A breakdown voltage test, often called BDV, measures the voltage at which an electrical arc forms through an oil sample under controlled conditions. It is a proxy for dielectric strength and sensitivity to moisture, particles, and contamination. Lower BDV typically indicates higher water content, suspended solids, or degraded oil that can reduce insulation margins. BDV is useful for trending and for acceptance testing of new or treated oil, but it should be interpreted alongside moisture, tan delta, and DGA for a complete view.