    How is an acidity test on transformer oil performed?

    #3663
    Galasso Guidone
    Participant

    Acidity is measured by titrating an oil sample with a standardized alkaline solution and determining the neutralization number, expressed in mg KOH per gram of oil. The test indicates the amount of acidic oxidation byproducts present. Rising acidity signals oil aging and increased risk of sludge formation, corrosion, and dielectric degradation.