How to conduct an oil BDV test of transformer before energization?

Home FAQ Transformer Oil Maintenance How to conduct an oil BDV test of transformer before energization?

Viewing 2 posts - 1 through 2 (of 2 total)
  • Author
    Posts
  • #1746
    Galasso Guidone
    Participant

    How to conduct an oil BDV test of transformer before energization?

    #1747
    Falcó Cruz
    Participant

    After oil treatment, take a sample and test using a calibrated BDV tester with a 2.5 mm gap. Breakdown voltage should be ? 60 kV. Fluidex units include inline sampling ports and offer optional BDV testers for fast validation before transformer start-up.

Viewing 2 posts - 1 through 2 (of 2 total)
  • You must be logged in to reply to this topic.