How to perform a breakdown voltage test after transformer oil filtration?

Home FAQ Transformer Oil Maintenance How to perform a breakdown voltage test after transformer oil filtration?

Viewing 2 posts - 1 through 2 (of 2 total)
  • Author
    Posts
  • #1636
    井上 零
    Participant

    How to perform a breakdown voltage test after transformer oil filtration?

    #1637
    Marciano Girona
    Participant

    After filtration, collect an oil sample in a hermetically sealed BDV test cell. Test using a calibrated BDV tester with standard electrode gap (2.5 mm). Fluidex offers test kits and processing units with built-in BDV sampling ports. Typical target is ? 60 kV for new or well-treated oil. A successful BDV test confirms the oil’s insulation strength.