What faults can transformer oil dissolved gas analysis detect?

Home FAQ Transformer Oil Maintenance Transformer Oil What faults can transformer oil dissolved gas analysis detect?

Viewing 2 posts - 1 through 2 (of 2 total)
  • Author
    Posts
  • #2512
    Hidde
    Participant

    What faults can transformer oil dissolved gas analysis detect?

    #2513
    Joseph
    Participant

    DGA can detect partial discharge, low temperature overheating, high temperature overheating, and arcing faults inside a transformer. Hydrogen often relates to partial discharge, methane and ethane to lower temperature thermal faults, ethylene to higher temperature overheating, and acetylene strongly indicates arcing. Carbon monoxide and carbon dioxide indicate paper insulation degradation. DGA also helps detect evolving faults by trending gas generation rates over time, allowing intervention before protection trips or major damage occurs.

Viewing 2 posts - 1 through 2 (of 2 total)
  • You must be logged in to reply to this topic.

Become a Fluidex dealer ?